There is a significant number of nodes down along with no response to remote management.Staff is enroute to the DC to check what is going on.UPDATE 1: AC Unit had failed, which had caused some servers to go full power on fans, which in turn caused couple single rack single phases to trip, causing switches to be down, causing larger number to fail. ... Read More »
Unfortunately our support response times are a little bit prolonged at this time, we expect the situation to ease by end of the week.
These were publicized without our prior knowledge of them about to be published, the fixes should have been properly tested upfront but are now being implemented without testing.Somethings are almost guaranteed to break, and somethings will become harder to manage.These changes also allows server abusers to get away much easier.Someone publicized ... Read More »
The entire rack LE6 is down. If the service hostname starts with LE6 it is affected.Some servers are down, others are up. Looks like electrical issue.On-site intervention underway.UPDATE 14:03 11/03/2022: Issue fixed. A switch PSU had failed and caused fuse for 1 phase to trip. Approx usage was ~3.3A on a 16A circuit. Dual PSU switch so rest of ... Read More »